Based on digital microprocessor technology, the MH REF 052n is designed as a universal earth fault protective relay, integrating selectable time earth fault characteristic curves. With digital processing of input values, the MH REF 052n offers high measuring accuracy and a wide setting range in fine resolution.

Mechanical Trip Button (MTB):

FEATURES:

  • Microprocessor-based with highest accuracy
  • Mechanical Trip Button (MTB) fault indication system
  • No requirement for auxiliary power supply for fault indication
  • Safeguard against automatic reset before fault rectification
  • Curve selection In accordance with ANSI, IAC, IEC, 1.3/10, Hong Kong Utilities Curve
    • Normally Inverse (Nl) 
    • Very Inverse (VI)
    • Extremely Inverse (El)
    • Short Time Inverse (STl)
    • Moderate Inverse (Ml)
  • Trip value recording (4-memory)
  • Date and time stamping for tripping
  • Integrated surge arrester against transient overvoltages
  • High set mode is Incorporated for instantaneous protection
  • Tamper-proof design for settings protection
  • Serial Interface RS485 for Modbus RTU communication (optional)
  • Type tested for EMC compliance In acc. with IEC 61000
  • High immunity to electrical Interference (tested to 2.5GHz)
  • Type tested In acc. with IEC 60255
  • Comply to ANSI 86, ANSI 51N/51G, and ANSI 50N/50G

MTB:

  • Protrude out when relay triggered
  • Hold on status without power supply
  • Push back in to reset

TECHNICAL DATA:

Power supply

  • AC/DC 85 - 265V (other voltages available on request)

Operating frequency

  • 50/60HZ

Earth fault setting

  • 2.0 - 50.0% in step of 0.1%

Time multiplier setting

  • 0.03 - 2.00 in step of 0.01 (IEC, 1.3/10)
  • 0.3 - 20.0 in step of 0.1 (ANSI, IAC)

Definite time delay setting (DTL)

  • 0.03 - 2.00 sec in step of 0.01 sec

Instantaneous Mode (High Set)

  • 2.0 - 10.0 times setting current in step of 0.1

Pick-up current

  • 100 - 115% of the setting current in step of 1%

Reset current value

  • <90% of the operating value

Working temperature range

  • -10°C to 55°C

Storage temperature range

  • -20°C to 65°C

Relative humidity (IEC 60068-2-30)

  • 95% at +40°C

Protection Class (IEC 60529)

  • IP54 (optional with IP65 front cover)

Overcurrent with stand ability

  • 20A for 3 sec

Power consumption

  • <6VA

Relay Output

  • 1 x C/0 (Changeover),
  • 1 x N/0 (Normally Open)

Contact Rating

  • 5A at 250VAC

Electrical Life

  • 1 x 105

Mechanical Life

  • 5 x 105

Optional interface

  • RS485 to Modbus RTU/Slave

LED status indication

  • Normal operation, fault current detected

Safety feature

  • Mechanical Trip Button (MTB) complying with ANSI 86

Housing material

  • ABS resin complying with UL94VO

Net weight

  • Approx. 390g

COMPLIANCE WITH STANDARDS:

IEC/EN 61000 -4 -2

Electrostatic discharge immunity test

IEC/EN 61000 -4 -3

Radiated, radio-frequency, electromagnetic field immunity test

IEC/EN 61000 -4 -4

Electrical fast transient/ burst immunity test

IEC/EN 61000 -4 -5

Surge immunity test

IEC/EN 61000 -4 -6

Immunity to conducted disturbances, induced by radio -frequency fields

IEC/EN 61000 -4 -8

Power frequency magnetic field immunity test

IEC/EN 61000 -4 -11

Voltage dips, short interruptions and voltage variations immunity tests

IEC/EN 60255 -1

Measuring relay and protection equipment

IEC/EN 60255 -21 -1

Vibration tests

IEC/EN 60255 -21 -2

Shock and bump tests

IEC/EN 60255 -26

Electromagnetic compatibility requirements

IEC/EN 60255 -27

Product safety requirements

CISPR 11 /EN 55011

Electromagnetic compatibility (EMC)

 
ORDERING INFORMATION:
 

Model

Description

REF 052n

MTB IDMTL EF relay, panel type

MD05

2 NO contacts module

(1 NO contact for OC, 1 NO contact for EF)

MD01

RS485 module

 
HƯỚNG DẪN CÀI ĐẶT RELAY REF052n:
 

Danh mục sản phẩm

Giải pháp của chúng tôi

Bài viết gần đây

Lịch nghỉ tết Ất Tỵ năm 2025

Mun Hean kính gửi quý khách hàng lịch nghỉ tết Ất Tỵ 2025!

DỊCH VỤ ĐÁNH GIÁ HỆ THỐNG THU SÉT PHÁT TIÊN ĐẠO...

Khi hệ thống chống sét truyền thống dựa trên nguyên lý Franklin...

0848116600